Flowcont UN

Flowcont UN

Compact or seperate, magnetic inductive flowmeter

Inquire now

Advantages
  • The Flowcont® FN offers a wide range of process connection, nominal diameters and high resistive coating up to 180°C
  • The new measuring sensor has a short response time due to his high exciting frequency
  • Due to modern filtering technologies the measuring and interfering signals can be separated exactly. This allows a highly precise measuring also at difficult conditions
  • Selfcleaning electrodes with double sealing guarantees a high reliability of the flow meter
  • Due to the grating strengthened coating in PFA the device is vacuum stable and can be used up to 180°C
Function description

The Flowcont® FN is featured especially by his backlight illuminated display. 

Many features can be set by the user:

  • contrast
  • configurable display
  • character size
  • number of lines

In the multiplex mode different display settings can be preconfigurated, that can be activated in succession.

The "SensorMemory", that is integrated in the sensor, makes the control of the assignment of measuring sensor and measuring transmitter unnecessary.

After power on the auxiliary power the sensor data and the measuring place specific parameter will be loaded automatically. Thus, errors will be eliminated, the inauguration goes faster and safer and avoids problems.

Diagnosis functions monitors the functionability of the Flowcont FN and the engineering of the process. The limit values of the diagnosis parameter can be set in the operation field. At exceeding this limit values an alert occurs. For further analysis the diagnosis data can be read out by a modern infrared interface. This allows a higher productivity and avoids downtimes. The state messages are classified corresponding to the requirements of NAMUR NE107.

In the case of an error in the display a diagnosis dependent message, that makes the error elimination much easier and faster. This offers a maximum safety in the process.

  • resolution of the display (number of fractional digits)
Technical Data

Measuring principle: Ultrasonic sensor

Medium: Fluids

Nominal width measuring tube: NW 10 / NW 15 / NW 20 / NW 25

Process temperature: 0 °C ... +80 °C

Process pressure: NW 10 und NW 15: Max. 10 bar / NW 20 und NW 25: Max. 6 bar

EHEDG approval: yes

Minimum flow: NW10: 0.3 l/min NW15: 0.9 l/min NW20: 3.5 l/min NW25: 5 l/min

Maximum flow: NW10: 21 l/min NW15: 36 l/min 6 NW20: 0 l/min NW25: 240 l/min

Inlet zone: NW10: 10 cm NW15: 30 cm NW20: 50 cm NW25: 80 cm

Outlet zone: NW10: 0 cm NW15: 5 cm NW20: 10 cm NW25: 20 cm

Conductivity: No limitation

Accuracy: 2 % (of final value)

Reproducibility: 0.5 %

Resolution: NW 10:0.003 l/min; NW 15: 0.006 l/min; NW 20: 0.012 l/min; NW 25:0.03 l/min

Process connection:
NW 10 G 1/2, 1/2“ NPT, Clamp 11864
NW 15 G 3/4, 3/4“ NPT Clamp 11864
NW 20 G 1, 1“ NPT Clamp 11864
NW 25 G 1 1/4, 1 1/4 “ NPT Clamp 11864

Wetted parts: PSU

Housing material: PSU

Weight: NW10: 340 g; NW15: 350 g, NW20: 420 g; NW25: 460 g

Supply voltage: 18 V DC ... 30 V DC

Ripple: ≤ 5 Vpp

Power consumption: ≤ 180 mA

Initialization time: ≤ 5 s

Protection class: III

Electrical connection: M12x1, 5-pin / M12x1, 8-pin (depending on type)

Impuls/frequency output: 0 kHz ... 10 kHz

Signal voltage: HIGH: Vs - 2 V, LOW: ≤ 2 V

Output current: < 100 mA

Load: inductive: 1 H; capacitive: 100 nF

Response time: Filter off 100 ms, filter low 300 ms, filter medium 1 s, filter strong 4.2 s

Enclosure rating: IP 67

Output load: < 500 Ohm

Signal level: Lower: 3.8 mA ... 4 mA; upper 20 mA ... 20.5 mA

Ambient temperature operation: 0 °C ... +60 °C; storage –20 °C ... +70 °C