IEC/EN60204-1:2016 and low voltage switchgears and controlgears IEC/EN61439-1-2:2011

Inquire now
  • HT Instruments offers a cutting-edge device to carry out all measurements required by the new laws as regards tests to be performed on electric switchboards and machines IEC/EN60204-1:2016 and IEC/EN61439--2:2011.

  • Further to measurements of protective conductors’ continuity, insulation and dielectric strength, FULLTEST3 is capable of carrying out tests on RCDs type A, AC and B, General, Selective and Delayed, measurements of Line/Loop impedance also with high resolution 0.1mΩ (with optional accessory IMP57), measurement of non-trip earth resistance and leakage current with clamp transducer.


IEC/EN60204-1:2016 Measuments:

Power Frequency Dielectric withstand voltage with test voltage of 1000VAC

Testing protection against indirect contact:

  • Continuity of protective conductors with test current 200mA
  • Automatic disconnection of the supply (RCD, MCB, Fuse)?
  • RCD tripping (RCD AC, A, B) up to 1A on TT Systems
  • Magneto-thermal protections (MCB curve verificaiton on B, C, D, K) and fuses (gG, aM) on TN Systems

Insulation resistance measurement with test voltage of 500VDC

Discharging of residual voltage V<60V in 5sec/1sec

Functions
Continuity of protective circuit with 200mA  
Continuity of protective circuit with I>10A, V<12V  
Continuity of protective circuit with I>25A, V<12V  
Insulation with test voltages 100, 250, 500, 1000VDC  
Dielectric strength with voltage programmable from 250V to 5100VAC  
Discharge time/residual voltage on plugs and internal circuits  
Absorbed/leaked current and power at plug of machines  
Tripping time/current of type A, AC, B General and Selective RCDs up to 1000mA  
Contact voltage  
Line/Loop impedance and Ipsc calculation  
Line/Loop impedance with high resolution (with optional accessory IMP57)  
Non-trip earth resistance  
Leakage current (with optional accessory HT96U)  
Phase sequence  
Timer and limit thresholds selectable through programmable ramps  
USB interface Collegamento ad accessori opzionali
Provided PC interface with software for Windows  

It can also carry out test on breaking capacity, protection tripping, I2t tests relevant to magneto-thermal circuit breakers in curve B, C, D, K and fuses type gG and aM. The device is also provided with a “touch-screen” colour display and 3 USB ports for connection to PC, USB pen drive, USB printers and possible bar code readers.

IEC/EN61439-1-2:2011 Measurements:

Clearances and Creepage distances:

  • Dielectric withstand voltage with test voltage of up to 3400/5100VAC

Continuity of earth system and protective conductors ≥10A

Power Frequency Dielectric withstand voltage with test voltage of 1800VAC

Alternative power-frequency voltage test up to 5100VAC

Test on enclosures of insulating material:

  • Dielectric Withstand voltage with test voltage up to 2835V

Discharging of residual voltage V<60V in 5sec/1sec

Guidelines
CEI 64-8
CEI 64-8/7
CE MARK
EMC 2014/30/EU
EMC: IEC/EN61326
EN50106
IEC/EN60204-1
IEC/EN60598-1
IEC/EN61010-1
IEC/EN61187
IEC/EN61335-1
IEC/EN61439-1
IEC/EN61439-2
IEC/EN61557-1
IEC/EN61557-13
IEC/EN61557-14
IEC/EN61557-2
IEC/EN61557-3
IEC/EN61557-4
IEC/EN61557-6
IEC/EN61557-7
LVD 2014/35/EU
UNE20460