Hit Enter to Search
Gas Sense GS-ADR.BC.V-1

Gas Sense GS-ADR.BC.V-1

Addressable gas detector for combustible gases

Inquire now
  • Addressable gas detectors GS-ADR.BC.V are intended for monitoring of combustible gases.

  • Different principles of detection with catalytic, semiconductor or electrochemical sensor elements are used.

  • Reliable operation of the sensor is guaranteed by the self diagnostic function.

  • The condition of the sensor element is constantli monitored and alert is activated in case of fault.

  • Sensor calibration is done remotely with magnetic key without opening the enclosure that facilitates periodic test and callibration.

  • Gas detectors GS-ADR.BC.V are in IP65 rated metal housing.


Application
Addressable gas detectors GS-ADR.BC.V are designed to monitor the concentration of explosive gases and vapors.
Along with addressable gas controllers GA-ADR.E1 they can be integrated into the overall building automation system.
Detected gases Formula Measuring range Order code
METHANE   0 - 100% LEL GS-ADR.BC.V.CH4.100
PROPANE   0 - 100% LEL GS-ADR.BC.V.PRO.100
N-BUTANE   0 - 100% LEL GS-ADR.BC.V.PRO.100
N-PENTANE   0 - 100% LEL GS-ADR.BC.V.PEN.100
N-HEXANE   0 - 100% LEL GS-ADR.BC.V.HEX.100
N-HEPTANE   0 - 100% LEL GS-ADR.BC.V.HEP.100
N-OCTANE   0 - 100% LEL GS-ADR.BC.V.OCT.100
METHANOL   0 - 100% LEL GS-ADR.BC.V.MNL.100
ETHANOL   0 - 100% LEL GS-ADR.BC.V.ETL.100
ISO-PROPANOL   0 - 100% LEL GS-ADR.BC.V.IPR.100
ACETONE   0 - 100% LEL GS-ADR.BC.V.ACE.100
METHYL ETHYL KETONE   0 - 100% LEL GS-ADR.BC.V.MEK.100
TOLUENE   0 - 100% LEL GS-ADR.BC.V.TOL.100
ETHYL ACETATE   0 - 100% LEL GS-ADR.BC.V.EAC.100
HYDROGEN   0 - 100% LEL GS-ADR.BC.V.HYD.100
AMMONIA (LEL)   0 - 100% LEL GS-ADR.BC.V.AMM.100L
UNLEADED PETROL   0 - 100% LEL GS-ADR.BC.V.UPT.100
ETHYLENE   0 - 100% LEL GS-ADR.BC.V.ETH.100
Sensors for gases, not listed in the table are made with preliminary order.
TECHNICAL SPECIFICATIONS
  • detection principle: semiconductor, catalytic, electrochemical

  • measuring range: 0–100% LEL

  • output signal: RS485

  • working voltage: 12÷30VDC

  • power consumption: < 2W

  • weight: 0.520 kg

  • sizes: 155 x 95 x 48 mm

  • enclosure material: aluminium

  • ingres protection: IP65

  • cable glands: 1/2/3 - ?16/M20

  • working temperature: -20 ÷ + 50 ºC

  • humidity: 30 ÷ 90% RH

  • pressure: 1 bar ± 20%

  • sensor life: til 5 years for semiconductor and catalytic sensors

  • meets the requirements of EN 50270

  • ATEX certification:

  • II 2G Ex ma (ib) e IIC T4 Gb

  • II 2D Ex to(ib)ma IIIC T135C IP65 Db