Hit Enter to Search
GS-220.B.V

GS-220.B.V

Digital gas detector

Inquire now
  • Gas detectors GS-220.B.V are monitoring levels of combustible, toxic or refrigerant gases.

  • Different principles of detection with catalytic, semiconductor or electrochemical sensor elements are used.

  • Reliable operation of the detector is ensured by the self-diagnostic function, which constantly monitors the condition of the sensor and signal lines and alerts in case of fault.

  • Sensor calibration is done remotely with magnetic key without opening the enclosure that facilitates periodic inspection and maintenance.

  • Gas sensors GS-220.B.V are in a metal housing with IP 65.


Application
Gas Sensor GS-220.B.V is intended for detection and measurement of combustible, toxic or refrigerant gases.
Detected gases Formula Measuring range Order code
Ammonia NH3 0 - 100% LEL GS-220.B.V.02-
Acetilene C2H2 0 - 100% LEL GS-220.B.V
Acetone (CH3)2CO 0 - 100% LEL GS-220.B.V
Hydrogen ?2 0 - 100% LEL GS-220.B.V
Ethanol C2H5OH 0 - 100% LEL GS-220.B.V
Methane CH4 0 - 100% LEL GS-220.B.V
LPG   0 - 100% LEL GS-220.B.V
Hexane C6H14 0 - 100% LEL GS-220.B.V
Carbon monoxide CO 0 - 500 ppm GS-220.B.V
Carbon dioxide CO2 0 - 15000 ppm GS-220.B.V
Hydrogen sulphide H2S 0 - 100 ppm GS-220.B.V
Oxygen O2 0 - 25 %v GS-220.B.V
Freons   0 - 2000 ppm GS-220.B.V
Sensors for gases, not listed in the table are made with preliminary order.
TECHNICAL SPECIFICATIONS
  • measurement principle: semiconductor, catalytic, electrochemical

  • measuring range: depends from the detected gas

  • output signal: digital

  • working voltage: 12V÷30VDC

  • power consumption: < 2W

  • weght: 0,520 kg

  • sizes: 155 ? 95 ? 48 mm

  • enclosure material: aluminium

  • ingress protection: IP65

  • cable glands: 1/2/3 - ?16/M20

  • working temperature: -20 ÷ + 50 ºC

  • humidity: 30 ÷ 90% RH

  • pressure: 1 bar ± 20%

  • runtime: till 5 years under standard conditions for semiconductor and catalityc sensors

  • meets the requirements of EN 50270

  • ATEX certification: EX II 2G Ex Ia IIC T5