The advantages at a glance
  • Data logger with remote data transmission

  • For 2" level pipe installation

  • Connection of e.g. level sensors and ultrasonic sensors (such as Hydrolog HP4 and Sonicont USP4)

  • Bluetooth and cellular (GSM, LTE)

  • Provider-independent - the strongest provider on site is chosen

  • Configurable via app

  • Redundancy function of the measurement

  • Memory for 500,000 measured values

  • 5 sensor inputs (2x 4 ... 20mA, 2x Modbus, 1x switching input)

  • Battery or accumulator operation

  • External DC supply

  • PV module connection

  • IP68 - flood-proof up to 3m water column

  • Materials approved for drinking water

Hilfsenergie

Batterie B1

Lithium / 3,6V-19Ah

Batterie B2

Lithium / 3,6V-35Ah

Akkumulator A1

LiION / 4,2V-10Ah

Versorgungsspannung DC

7…32VDC / ≤ 350mA

PV-Modul

4,5…35VDC / ≤ 1A

Eingang COM CI1 / CI2

Schnittstelle

RS485, bidirektional / Modbus®-RTU / 9600 Baud (4800…38400 Baud)

Eingangswiderstand

96k?

Eingang Analog AI1-I / AI2-I

Referenzbedingungen

EN/IEC 60770-1: Kennlinienabweichung – Grenzpunkteinstellung

15..25°C / 860..1060kPa / 45..75%r.F. / ton240s / Batterie 35Ah

 

Kennlinienabweichung = Nichtlinearität + Hysterese + Wiederholbarkeit

FSI = Full Scale Input = Nennmessspanne

Arbeitsbereich

FSI 0…28mA / Ri 27R

Auflösung

FSI 16 Bit

Kennlinienabweichung

≤ ±0,05% FSI

Temperaturabweichung

≤ ±0,1% FSI / 10K

Langzeitdrift

≤ ±0,05% FSI / Jahr

Eingang Digital DI1

Arbeitsbereich

≤ 20kOhm / ≤ 1kHz

Messumformerversorgung

Ausgangsspannung UO1 / UO2

16,6V ±0,3V (0mA) / 15,9V ±0,3V (30mA) / 0…30mA, max. 40mA

Ausgangsspannung UO3 / OU4

6,7V ±0,2V (0mA) / 6,6V ±0,2V (100mA) / 0…100mA, max. 300mA

Interface Bluetooth

Version

Bluetooth 5.0 LE (2Mbit/s, Advertising Mode 2s)

Sendeleistung

≤ 0,1W

Reichweite

Outdoor max. 200m / Indoor max. 40m

Interface 4G/2G

Version

4G LTE Cat. 1 (B3, B8, B20)

2G EDGE, GSM, GPRS (900MHz/1800MHz)

Sendeleistung

4G ≤ 0,2W

2G ≤ 2W

SIM

Interne SIM + Externe Micro-SIM

Antennenanschluss

Stecker SMA / 50Ohm

Datenspeicher

Speichergröße

8MB, ≥ 800.000 Messwerte

Clock

Ganggenauigkeit

≤ ±1 Minute / Monat

Umgebungsbedingungen

Umgebungstemperatur

-20°C...+60°C

Schutzart

IP68 [≤3m/≤0,3bar] (EN/IEC 60529)

Klimaklasse

4K4H (EN/IEC 60721-3-4)

Stoßfestigkeit

15g [11ms] (EN/IEC 60068-2-27)

Schwingungsfestigkeit

4g [10…2000 Hz] (EN/IEC 60068-2-6)

EM – Verträglichkeit

Betriebsmittel Klasse B / Industriebereich (EN/IEC 61326)

MTTF

258 Jahre

Gewicht

0,9kg

Werkstoffe

prozessberührend

PA, Aluminium, PUR, Messing, Nickel, Silikon, NBR

Applications

The Hydrolog HLF4 is used for measured value recording and remote data transmission from level probes, ultrasonic sensors or similar level sensors.

A new and innovative redundancy function makes it possible to have the Hydrolog HLF4 automatically verify measured values. The recorded data are cyclically transferred to the ACS portal on the Internet. There they can be analysed and processed by the authorized user from any location.

The areas of application range from groundwater monitoring, surface water measurement, landfill monitoring, to rainwater overflow logging.

The well thought-out alarm management enables the danger of flooding or even low water to be eliminated or reduced.

Function

The battery operated data logger serves as a link between the measuring point e.g. with a level sensor from the Hydrolog® series and the data platform on the Internet.

Depending on the setting and sensor, a battery can achieve a service life of more than 5 years. It is possible to operate the Hydrolog HLF4 using an external power supply or PV modules instead of batteries.

The data transfer to the ACS portal on the Internet is carried out automatically by the strongest mobile operator on site. It does not matter whether there is 2G GSM or 4G LTE network coverage. The SIM card is already integrated in the device. The user does not need any further mobile phone contracts.

The multifunctional input makes it possible to connect standard sensors as well as energy-saving digital sensors.

The built-in redundancy function makes it possible to compare two measured values from different sensors. This means that measured values can be verified and an alarm is triggered automatically at an adjustable difference. This results in the highest level of measurement reliability combined with a minimum of control measurements.

Operation on site is via a Bluetooth interface in connection with an app. No special devices are required for this. A smartphone, tablet or laptop is sufficient for operation.