Pressure transmitter for measurement of relative pressure in gases, vapors, liquids and dust - even from harzadous areas
Inquire now
Advantages |
Application description |
The device is an electronic pressure transmitter / pressure switch for monitoring, control and continuous measurement of pressures.
The pressure transmitter is suitable for demanding measuring requirements, especially at constricted installation situations and high temperature stress.
Due to its high accuracy and the digital adjustability by HART® the device can be suited to a wide variety of applications.
The robust design and the high-quality workmanship turns the device into a very high quality product, which even the most adverse environmental conditions cannot affect, whether the lowest temperatures when used outdoors, extreme shock and vibration stress or aggressive media.
A captive laser marking of the type label ensures the identifiability throughout the entire lifetime of the device.
Obviously is the optional marking of a measurement point designation resp. TAG, a customer label or of a neutral type label, of course also per laser marking.
A factory calibration with calibration certificate and a customer specific configuration resp. preset is also optionally available like factory certifications for drink water suitability.
Customer specific special versions can be realized on request, e.g. special designs for the process connection or other process materials.
Technichal data |
Measuring range
Nominal pressure PN 0…10bar to 0…600bar
Output type A – Current 4…20mA HART®
Analogue output 4…20mA 3,9…20,5mA / ≥ 3,8mA / ≤ 22mA / dI ≤ 1µA
Time behavior T90 ≤ 10ms / ton ≤ 0,2s
Interface HART®-compliant (7.0) / 1200 Bit/s
Auxiliary power
Supply voltage Us polarity protected Type A – 4…20mA HART®: 9…35VDC / Ex: 9…30VDC
Measuring accuracy
Characteristic deviation ≤ ±0,15%/±0,5%FSO
Long term drift ≤ ±0,2%FSO/year
Temperature deviation Tk Zero ≤ ±0,015%FSO/K / Tk Span ≤ ±0,015%FSO/K
Process conditions
Process temperature Standard: -40°C...+125°C / Extended: -40°C...+200°C
Pressure cycles ≥ 100 Mio. (1,2xPN)
Environmental conditions
Environmental temperature -40°C...+125°C
Protection level IP69K/IP67 (EN/IEC 60529)
MTTF 463 years