Conductive electrode / Rod probe SAT

Inquire now
  • with synthetic thread

  • With up to 7 probe systems

  • Fluid Temperature: -40°C ... 150°C


Application description

The SAT rod probes are used in conjunction with the evaluation units (eg, SRA-100-U0) is used for level detection and level control in conductive liquids.

Depending on the number of bars and evaluation devices used, different measurement tasks such as Overflow, dry run, two-step control, moisture detection, etc. are realized.

Depending on model selected can include the container wall as a mass, to be implemented to 7 switch points. The ground connection erflogt either directly to the container or conducting a probe rod.

In the probe head, an additional module (diode module LBM) for permanent circuit monitoring to be installed.

In the case of a line break between the electrode probe and an appropriate evaluation, the evaluation issue an alert.

Technichal Informations

Operating pressure: -1 ... 10 bar

Temperature range: -40°C ... +150°C, observe limitations (see operating instructions)

Protection: IP65 EN/IEC 60529

Material connection: POM / PP / PTFE

Probe material: Stahl 1.4404 (AISI316L) bzw. 1.4571 (AISI316Ti) / Hastelloy C22

Isolation probe rod: PA / ETFE bzw. E-CTFE

Gaskets (medium contact): Electrode isolation PA: NBR / Electrode isolation ETFE bzw. E-CTFE: FPM